Water Supply and Distribution Flashcards
View Flashcards → Download as-is, or customize
to fit your needs.
About:
This 32-card set covers water supply and distribution systems, including plumbing codes, backflow prevention assemblies, water pressure standards, and piping requirements. It addresses barometric loops, dielectric unions, cross-connections, and regulatory specifications. Use it for plumbing certification exam preparation or professional reference during code-compliance training.
Terms in This Set
- 1.)URINALS REQUIRE A WATER SUPPLY W/ A MINIMUM DIAMETER OF__C.)3/4 OF AN INCH
- 2.)WHICH OF THE FOLLOWING PERTAINS TO A CODE REQUIREMENTON THE USE OF FLEXIBLE WATER CONECTIONSA.)FLEXIBLE WATER CONNECTIONS MUST BE READILYACCESIBLE TO THE FIXTURE
- 3.)THE MAXIMUM WATER PRESSURE IN RESIDENTIAL WATER DISTRIBUTION SYSTEMS IS C.)80 POUNDS PER SQUARE INCH
- 4.)A BAROMETRIC LOOP IS__ABOVE THE HIGHEST PIPINGA.)33.9’
- 5.)A PRESSURE VACUUM BREAKER IS LISTED FOR C.)BACKSIPHONAGE ONLY
- 6.)SILL COCKS REQUIREA.)A BACKFLOW PREVENTER
- 7.)METALLIC PIPE OR CONNECTOR IS REQUIRED TO CONNECT TO A WATER HEATER AND IT MUST RISE TO A POINT AT LEAST__INCHES ABOVE THE WATER HEATER BEFORE PEX TUBING OR PIPING CAN BE ATTACHED TO IT D.)18
- 8.)INLET AND OUTLET COPPER WATER CONNECTIONS TO AN ELECTRIC WATER HEATER SHOULD CONTAIN B.)DIELECTRIC UNIONS
- 9.)YOU WANT TO RUN A WATER SERVICE LINE ABOVE A SEWER PIPE IN THE SAME TRENCH. HOW MUCH DIRT MUST BE LAID BETWEEN THE PIPES?B.)12 INCHES
- 10.)A REDUCED PRESSURE PRINCIPLE ASSEMBLE IS LISTED FORB.)BACKSIPHONAGE AND BACKPRESSURE
- 11)IF A WATER SERVICE LINE AND A SEWER PIPE CANNOT BE INSTALLED IN THE SAME TRENCH AT DIFFERENT LEVELS.THEY CAN BE INSTALLED AT THE SAME LEVEL IN THE GROUND AS LONG AS__FEET OF EARTH SEPERATES THEM C.)5
- 12.)PURE WATER AT SEA LEVEL WEIGHS_POUNDS PER CUBIC FOOTB.)62.4
- 13.)THE MINIMUM SIZE OF A WATER SERVICE IS_B.)3/4’
- 14.)ANY AIR GAP HAS A MINIMUM REQUIREMENTOF ATLEAST 1” OR_ TIMES THE DIAMETER OF THE PIPEC.)2
- 15,) A NEGATIVE PRESSURE THAT CAN CAUSE BACKLFOW IS KNOWN AS:C.)BACKSIPHONAGE
- 16.)SOLDIER JOINTS SHALL BE ACCORDING TO ASTM B.)B-828
- 17.)THE COLOR__SHALL BE USED TO IDENTIFY RECLAIMED,RAIN, AND GRAY WATER DISTRIBUTION SYSTEMSD.)PURPLE
- 18.)FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING LOCATIONS:D.)ALL OF THE ABOVE
- 19.)SELECTING AN EXPANSION TANK IS BASED ONA.) WATER PRESSURE AND VOLUME
- 20.)FOR AUTOMATIC-CIRCULATING HOT WATER AND HEAT-TRACED SYSTEMS,PIPING SHALL BE INSULATED WITH NOT LESS THAN_INCH OF INSULATION C.)1
- 21.)THE WEIGHT OF THE COLUMN OF WATER ON FOOT HIGH COVERING A SQUARE INCH AREA WOULD BE __PSIA.)0.43
- 22.)THE AVB MUST BE INSTALLED W/ ITS CRITICAL LEVEL A MINIMUM OF__INCHES ABOVE THE HIGHEST DOWNSTREAM PIPING AND FLOOD LEVEL RIM OF RECEPTOR C.)6
- 23.)A __BACKFLOW PREVENTION ASSEMLBY CONSISTS OF TWO INDEPENDENTLY ACTING INTERNALLY LOADED CHECK VALVES, FOUR PROPERLY LOCATED TEST COCKS, AND TWO ISOLATION VALVES. B.)DOUBLE CHECK VALVE
- 24.)THE__IS APPROVED FOR BOTH LOW AND HIGH HAZARD PROTECTION.D.)BOTH B AND C
- 25.)A T&P OR RELIEF DISCHARGE PIPE LINE FROM A POTABLE WATER HEATER REQUIRES AN AIRGAP OF__INCHESB.)6
- 26.)A WATER CLOSET THAT IS EQUIPPED W/A BALLCOCK SHALL BE INSTALLED W/ THE CRITICAK LEVEL NOT LESS THAN_ INCH ABOVE THE FULL OPENING OF THE OVERFLOW PIPE A.)1
- 27.)THE MAXIMUM ALLOWABLE LEAD CONTENT IN PIPES,PIPE FITTINGS, PLUMBING FITTINGS, AND FIXTURES INTENDED TO CONVEY OR DISPENSE WATER FOR HUMAN CONSUMPTION SHALL BE NOT MORE THAN__PERCENT D.)0.25
- 28.)THE LEAD CONTENT SHALL BE NOT MORE THAN_PERCENT FOR SOLDER AND FLUX WHEN USED FOR HUMAN CONSUMPTIONA.)0.2
- 29.)FLEXIBLE METALLIC CONNECTORS THAT CONNECT A WATER HEATER TO THE PIPING SYSTEM SHALL NOT EXCEED__INCHES B.)24
- 30.)THE RESIDUAL WATER PRESSURE REQUIRED FOR ANY WATER SUPPLY SYSTEM IS__PSIA.)15
- 31.)UNIONS SHALL BE INSTALLED IN THE WATER SUPPLY PIPING NOT MORE THAN_INCHES OF REGULATING EQUIPMENT, WATER HEATING, CONDITIONING TANKS, AND SIMILAR EQUIPMENT THAT REQUIRES SERVICE BY REMOVAL OR REPLACEMENT IN A MANNER THAT WILL FACILITATE ITS READY REMOVAL B.)12
- 32.) ANY ACTUAL OR POTENTIAL CONNECTION OR STRUCTURAL ARRANGEMENT WHERE IT IS POSSIBLE TO INTRODUCE INTO THE POTABLE SYSTEM ANY USED WATER,INDUSTRIAL FLUID, GAS, OR SUBSTANCE OTHER THAN THE INTENDED POABLE WATER W/ WHICH THE SYSTEM IS SUPPLIES IS CALLED C.)CROSS-CONNECTION